How to Diagnostic and Repair PCC1302 PowerCommand Code 2972 – Field Overload

If the time that the Field AVR Duty Cycle is operating at maximum output is longer than the time in the “Max Field Time” parameter, event/fault code 2972 will become active.

Possible Causes:

CAUTION
Excessive voltage is possible during testing. Make sure your meter can handle
alternator full voltage.

1.Max Field Time Delay is set too low
2. Voltage sensing into the base board is too low, or there is an open/short circuit
3. Application issue

 

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

Diagnosis and Repair:
1 Max Field Time Delay is set too low
a Through the operator panel, check the “Max Field Time” parameter setting. Verify that the “Max Field Time” is not set to zero. The “Max Field Time” parameter may require adjustment to a value more appropriate for the application. To access the Max Field

Time configuration menu on the operator panel go to Setup > OEM Setup > OEM Alt Setup > Max Field Time and set the “Max Field Time” parameter appropriately for the application. Refer to the parameter list to see the default value for “Max Field Time”.

2 Voltage sensing into the base board is too low, or there is an open/short circuit

a Measure the voltage going into the base board at L1 = J22-1, L2 = J22-2, L3 = J22-3,and LN = J22-4 (for single phase applications use L1, L2 and LN). If the generator set control is not sensing voltage, it will try to overcompensate by maxing out the AVR output. If the voltage going into the control board is zero, or less than the voltage that the control was calibrated for (Nominal Voltage), then check the wiring from the alternator to the base board for an open circuit or short circuit.

b If the generator set is over 600 VAC, check connections from the alternator to the PT,and from the PT to the base board. If there is voltage going into the PT, but not coming out of the PT, replace the PT.

Measure the output of the AVR at J17 -1 and J17-2 while turning the generator set on.
The output should be at least 300 VDC when the generator set is starting, but the voltage should decrease significantly when the generator set builds up voltage. If the output of J17-1 and J17-2 is constantly high or is locked in, then the AVR portion of the PCC is faulty. Replace the base board if the AVR is faulty.

3 Application issue
a. If the generator set runs adequately with no load or some load but as soon as additional load is applied, the generator set shuts down on “Field Overload”; then this
might be an application issue (load issue, generator set undersized, etc.).

 

Refer to the engine manual for correct threshold values and make the appropriate changes using InPower v14.5 pro.

auto

Recent Posts

How to Replace Fuel Tank Breather Filter Element for Liebherr R9600 Excavator

Here is the instruction show you guide on how to replace fuel tank breather filter…

3 days ago

FENDT 900 Vario COM III B092 Boost Pressure/Temperature Sensor

FENDT 900 Vario COM III tractor Component B092 - Sensor, charge air pressure/temperature reports the boost…

6 days ago

Deutz EMR3 Engine Trouble Code 87 / 97 / FlFCD WATER IN FUEL Solution

Deutz EMR3 Engine Trouble Code 87 / 97 / FlFCD WATER IN FUEL Solution Error description…

1 week ago

Kubota L3301 L3901 Tractor Hydraulic Flow Test Guide

This instruction show you guide on how to perform hydraulic flow test for Kubota L3301…

3 weeks ago

Bendix AutoVue FLC20 Camera LDW Configuration by JPRO

This instruction show you guide on how to configure Lane Departure Warning for Bendix AutoVue…

3 weeks ago

How to Solve AGCO Machine SPN 102 FMI 03 Boost Pressure Sensor Defect HIGH

This instruction show you guide on how to solve AGCO machine SPN102 FMI03 boost pressure…

3 weeks ago