Heavy Equipment Repair

How to Solve PCC1302 PowerCommand Remote Emergency Stop Activated

This instruction show you guide on how to solve PCC1302 PowerCommand remote emergency stop activated.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Logic:
The Remote Emergency Stop has been activated.
Possible Causes:
1. The Remote Emergency stop button has been activated
2. Faulty connection or faulty Emergency Stop switch

 

Diagnosis and Repair:
1 The Remote Emergency stop button has been activated
a. Reset the Remote Emergency Stop:
a. Pull the Remote Emergency stop button out.
b. Press the Off button.
c. Press the Reset button.
d. Select Manual or Auto as required.
b. If the Remote Emergency Stop is not used:
a. Install a jumper between the following:
TB1 – 16 Input
TB1 – 15 Ground
b. Reset the Remote Emergency Stop:
a. Pull the Remote Emergency stop button out.
b. Press the Off button.
c. Press the Reset button.
d. Select Manual or Auto as required.

2 Faulty connection or faulty Emergency Stop switch
a. Check the Emergency Stop button, and verify that it is working properly. The Emergency Stop button is a closed relay when it is pulled out (not active), and open
relay when depressed (active).
b. Verify that the connection/wiring from the Remote Emergency Stop switch to the PCC for an open circuit condition. A ground connection to the Remote E-Stop control input
(TB1 – 16 Input; TB1 – 15 Ground) disables the emergency stop alarm. An open
circuit should activate the Emergency stop alarm.
TB1 – 16 Input
TB1 – 15 Ground

auto

Recent Posts

AGCO EEM5 Stage V CORE 75-80 Supply Module

The supply module (SM) is a part of the vehicle SCR system. The SM is…

3 days ago

Yale G807 Brake System Air Bleed Guide

Yale G807 Brake System Air Bleed Guide   Related Contents: 2023 Yale PC Service Tool…

6 days ago

Bobcat G2 Stage V Engine P000F Common rail pressure Open Error Solution

This instruction show you guide on how to solve Bobcat G2 Stage V engine P000F…

1 week ago

How to Solve CASE 7120 IH 20 Series Axial-Flow Combine Creep Problem

Here is the instruction show you guide on how to solve CASE 7120 IH 20…

2 weeks ago

How to Jump-start Engine for MANITOU MT6034 Construction Telehandler

If the battery becomes discharged or does not have enough power to start the engine,…

2 weeks ago

Liebherr Machine P1121 DEF Pump Out of Service Error Solution

Here is the instruction show you guide on how to solve Liebherr machine trouble code…

2 weeks ago