PCC1302 PowerCommand Low Coolant Level (Warning or Shutdown) Solution
Related Contents:
2024 InPower V14.5 Pro V12 Diagnostic Software Free Download
PowerCommand Diagnostic 9 Pin Adapter Cable for InPower
Logic:
This fault is used when an optional coolant level sensor is installed. The nature of the fault is an optional customer selection.
The fault function can be programmed (using the InPower service tool), as follows:
• Enable/disable input (Default: enable)
• Status, Warning, or Shutdown (Default: #1-None, #2 and #3-Warning)
• Active closed or open (Default: closed [ground])
• Change the display name using up to 19 characters (Default: #1- Customer Fault 1, #2-Ground Fault, #3-Low Fuel)
Possible Cause:
1 Low coolant
2 No actual fault, external wiring problem
Diagnosis and Repair:
1 Low coolant
a If the generator set is powering critical loads and cannot be shut down, wait until next shutdown period, then do the steps that follow.
b Allow engine to completely.
c Check coolant level and replenish if low.
2 No actual fault, external wiring problem
a Disconnect the signal lead from TB1 and reset the control.
a CONFIG INPUT 1 – TB1-13
b If the message goes away, the external wiring has a short circuit. Grounding of either input activates fault.
This instruction show you guide on how to solve Scania truck motion and inclination detector,…
This instruction show you guide on how to solve JCB excavator 140 C130C-13 spool brake solenoid…
Scania truck fault in the CAN communication with the chassis management system (CMS),this instruction show…
The water pumps used on all Phaser/1000 Series engines have been changed. The changes to…
Here is the simple instruction on how to solve Deutz engine EMR3 trouble code 48…
CAT ET 2025A Power Shift Pressure Test function checks whether that the proportional reducing valve is…