How to Solve PCC1302 PowerCommand Engine Code 1447

This instruction show you guide on how to solve PCC1302 PowerCommand engine/generator fault code 1447 low AC voltage shutdown.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Logic:
One or more of the phase voltages has dropped to 85% of nominal for more than 10 seconds.

Possible Causes:
1 Fault simulation feature is enabled
2 Incorrect threshold setting or AVR settings
3 Overload
4 Improper connections at generator output terminals
5 The voltage sense or setup wiring connection could be incorrect
6 Damaged voltage regulator
7 The rotating rectifier assembly (diodes CR1 through CR6) is faulty

Diagnosis and Repair:
1 Fault simulation feature is enabled
a. Connect InPower.
b. Verify that the fault simulation is NOT enabled for the engine speed sensor by connecting to the PCC via InPower. If the fault simulation is disabled, there is no problem.

2 Incorrect threshold setting or AVR settings
a. Check threshold settings.
b. Connect InPower.
c. Verify that fault threshold is within the normal operating range for low AC voltage.
d. Verify AVR settings. Compare gains, settings, and calibration factors against default calibrations.
e. Adjust or recalibrate as necessary

3 Overload
a. Check for overload.
b. Check that load is within proper operating range.
c. Check inrush current.
d. Check for current spikes.

e.Check for motor starts.
f. Check operation by disconnecting the load and restarting the unit.
g. Correct any overload.

4 Improper connections at generator output terminals
a. Check connections.
b. Compare connections in generator to wiring schematic.
c. Correct according to the appropriate schematic as needed.

5 The voltage sense or setup wiring connection could be incorrect
a. Verify that the voltage sensing inputs J22-1, J22-2, J22-3, and J22-4 are connected to L1, L2, L3, and L4 respectively.
b. Verify that excitation inputs J18–1 and J18–2 are connected to the correct generator PMG terminals.

6 Damaged voltage regulator
a. Bring the generator to idle.
b. Connect InPower.
c. Using InPower, verify that the AC voltage output is greater than residual.
d. If the AC voltage output is residual, than the regulator is operating correctly.
e. Inspect the voltage regulator and the generator control harness connector pins.
f. Turn off the generator.
g. Disconnect the generator control harness from the voltage regulator.
h. Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins.

7 The rotating rectifier assembly (diodes CR1 through CR6) is faulty
a. Check each diode. See the alternator service manual.

auto

Recent Posts

Caterpillar C9 Engine Throttle Position Out of Calibration 28 91-13 Trouble Solution

This instruction show you guide on how how to solve trouble code 28 PID 91-13…

2 days ago

Magneti Marelli 1 AVB-VW ECU Pinout

Vehicles: With AP 1.6, 1.8 and 2.0 Ml engines DE 97 to 99. And for…

4 days ago

Valtra BH Series 140-210 Internal lateral Inertial Sensor Recalibration

This instruction show you guide on how to solve Valtra BH Series 140-210 trouble code SA…

5 days ago

Bendix AutoVue 3G LDW System Driver Assistance Systems (DAS) Tests

JPRO 2025V3 Driver Assistance Systems (DAS) Tests allows the editing of configuration parameters.   Related Contents:…

1 week ago

How to Solve PCC2300 PowerCommand Membrane Buttons Not Functioning

This instruction show you guide on how to solve PCC2300 Powercommand Membrane buttons not working.…

2 weeks ago

How to Solve JCB JS140 Excavator C101E Fuel Level Empty Alarm Error?

This instruction show you guide on how to solve JCB JS140 excavator C101E-68 fuel level…

2 weeks ago