PCC1302 PowerCommand Code 2729 2731 IO Module Lost Error Solution

Here is the instruction show you guide on how to repair PCC1302 PowerCommand Code 2729 2731 IO Module Lost Error.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Code 2729 – IO Module Lost (Warning)
Indicates an intermittent data link between the I/O module and the PCC control (Aux 101 I/O
Module option) and no input fault levels were set to Shutdown.

Possible Causes:
1. Incorrect Wiring
2. I/O settings misconfigured

Diagnosis and Repair:
1. Incorrect Wiring
a. Connection between AUX 101 and PCC 1302 is incorrect. Ensure proper wiring.
a. PCC 1302 TB1-1 – PCC Net A (+) to AUX 101 J1-3
b. PCC 1302 TB1-2 – PCC Net B (-) to AUX 101 J1-4
c. PCC 1302 TB1-3 – B+ Return to AUX 101 J14-2
d. PCC 1302 TB1-5 – Customer Fused B+ to AUX 101 J14-1
e. PCC 1302 TB15-5 – System Wake-up to AUX 101 J1-5
2. I/O settings misconfigured
a. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments > System I/O Adjustment > Output Relays ensure System IO Board Enable is disabled.
b. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments > System I/O Adjustment > ensure no inputs or outputs are configured as enabled.

Code 2731 – IO Module Lost (Shutdown)
Indicates an intermittent data link between the I/O module and the PCC control (Aux 101 I/O
Module option) and at least one input fault level was set to Shutdown.

Possible Causes:
1. Incorrect Wiring
2. I/O settings misconfigured

Diagnosis and Repair:
1. Incorrect Wiring
a. Connection between AUX 101 and PCC 1302 is incorrect. Ensure proper wiring.
a. PCC 1302 TB1-1 – PCC Net A (+) to AUX 101 J1-3
b. PCC 1302 TB1-2 – PCC Net B (-) to AUX 101 J1-4
c. PCC 1302 TB1-3 – B+ Return to AUX 101 J14-2

d.PCC 1302 TB1-5 – Customer Fused B+ to AUX 101 J14-1
e. PCC 1302 TB15-5 – System Wake-up to AUX 101 J1-5

2. I/O settings misconfigured
a. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments > System I/O Adjustment > Output Relays ensure System IO Board Enable is disabled.
b. If no AUX 101 is connected to PCC 1302, connect to InPower. Under Adjustments >System I/O Adjustment > ensure no inputs or outputs are configured as enabled.

 

Refer to the engine manual for correct threshold values and make the appropriate changes using InPower v14.5 pro.

auto

Recent Posts

How to Remove and Replace Cab Heater Controls for JCB 3CX Loader

Here is the instruction show you guide on how to remove and replace cab heater…

3 weeks ago

How to Remove Differential Gear for FENDT 900 Vario COMIII

Here is the instruction show you guide on how to remove differential gear for Fendt…

3 weeks ago

International MaxxForce 7 SPN 27 FMI 4 EGRP Signal Out of Range Low

This instruction show you guide on how to solve International MaxxsForce 7 SPN 27 FMI…

4 weeks ago

2025.08 BMW ISTA 4.54.40/4.02.14 ISTA-D Rheingold for BMW ICOM

BMW ISTA-D Rheingold 4.54.40/4.02.14 Standalone / SDP 4.02.13 / ISTA-P 3.60.0.600 free download link and…

4 weeks ago

Detroit DD13 SPN 84 FMI 3 MCM Vehicle Speed Sensor Open Circuit

This instruction show you guide on how to solve Detroit DD13 engine SPN 84 FMI…

4 weeks ago

How to Solve Caterpillar 24 PID 100-3 Oil Pressure Voltage High?

This instruction show you guide on how to repair Caterpillar 24 fault code,PID 100-3 oil…

1 month ago