PCC1302 PowerCommand CAN datalink communication has been lost between the generator set control and ECM,therefore event/fault code 2545 becomes active if event/fault code 781 “CAN Data Link Failure” is also active at the ECM.
Related Contents:
2024 InPower V14.5 Pro V12 Diagnostic Software Free Download
PowerCommand Diagnostic 9 Pin Adapter Cable for InPower
Possible Causes:
1 CAN datalink failure
2 Faulty ECM
Diagnosis and Repair:
1 CAN datalink failure
a Reset the Keyswitch manually.
a Put the generator set control in the OFF position and press the Reset button on the operator panel. This action will clear any shutdown faults and resets the Keyswitch.
b Enable the Keyswitch through the operator panel. Go to Test > Output > Engine > Keyswitch Driver Override Enable, set to Enable.
b Reset the ECM and PCC controls.
a Push the Emergency Stop button in.
b Wait 30 seconds.
c Disconnect the battery terminals from the battery.
d Wait 10-15 seconds.
e Reconnect the battery cables to the battery terminals correctly.
f Pull the Emergency Stop button out.
g Press the Fault Reset button.
c Check the relay that is proving power to the Keyswitch. This relay is normally open, and if faulty, replace.
d Check the terminating resistors. With connectors J11 and J26 removed, measure
resistance between pins J11-19 and J11-20 (60 ohms, is satisfactory).
e Reference the troubleshooting procedure for event/fault code 781 in the engine service manual.
2 Faulty ECM
a After ensuring that the ECM has an adequate B+ supply, connect to the ECM with InPower or Insite in order to determine if it is functioning correctly and can communicate with the PCC controller. Replace the controller if communication to it with InPower is not possible.
Refer to the engine manual for correct threshold values and make the appropriate changes using InPower v14.5 pro.
This instruction show you guide on how to remove second tank for CLAAS AXION 960-920…
This instruction show you guide on how to solve Doosan excavator P0408 maximum EGR rate…
Here is the instruction show you guide on how to calibrate 2403 steering valve for…
This function requires all connectors to be disconnected from all electrohydraulic valves on the tractor.You…
This instruction show you guide on how to remove center joint and center frame for…
How to solve Doosan heavy duty machine P0100 fault code signal error of air mass…