This instruction show you guide on how to solve PCC2300 Powercommand Membrane buttons not working.
Related Contents:
2025 InPower V16 Pro V12 Diagnostic Software Free Download
PowerCommand Diagnostic 9 Pin Adapter Cable for InPower
Logic:
Buttons on the membrane are not functioning or cannot naviagte through the screen menus.
Possible Causes:
1 Power is not present to the HMI.
2 Membrane navigation buttons are faulty.
Diagnosis and Repair:
1 Check the power supply to the HMI:
a Inspect if the connectors J28 and J29 are plugged in properly.
b Measure the voltage between pins J28-1 and J28-3. This should be done with J28 connected to the HMI. To test the voltage, place multimeter probes on the pins through the back side of J28.
If the voltage reading is 10–14 Vdc for a 12 Vdc system or 20–28 Vdc for a 24 Vdc system, the supply volatge is appropriate.
c If voltage value at J28 is out of specified range, check for voltage present at connector J25 pins
J25-8 (B+ return for operator panels) and J25-12 (Fused B+). J25 is the other end of J28 connector harness which completes the connection to PCC.
If this voltage lies between 10–14 Vdc for a 12 Vdc system or 20–28 Vdc for a 24 Vdc system, the connector J28 is faulty and needs to be replaced.
If the voltage value at J25 is out of the specified range, then the source battery voltage is low. Refer to troubleshooting for FC441 (Low battery volatge) if the FC is active. If FC441 is not active, replace the harness.
2 Membrane navigation buttons are faulty. Check the button functionality:
a Disconnect all connectors J28, J29 and TB15 from the back of the HMI.
b Reconnect connectors J28 and J29. This recycles power to the HMI.
c If the HMI has established communication with the PCC and the home menu is displayed, try to navigate through the menu using C, home, up, down left, right, OK and soft buttons.
d If the HMI is unable to establish communication with the PCC, disconnect connectors J28 and
J29 from the HMI. Reconnect only J28. Test the HMI in demo model.
To enable demo mode, press the “Home” and “C” buttons together for 3 seconds. Once this mode is activated, home menu comes up and “Demo Mode” is displayed at the top of the
screen.
Try to navigate through the menu using C, home, up, down left, right, OK and soft buttons.
If this can be done successfully, the membrane buttons are not faulty.
If the buttons still do not function, replace the HMI.
(Any changes made in the demo mode will not affect the controller. Power must be removed from the HMI to end demo mode).
If the demo mode cannot be enabled, the required buttons are not functioning. In this case,replace the HMI.
This instruction show you guide on how to solve JCB JS140 excavator C101E-68 fuel level…
Here is the instruction show you guide on how to solve AGCO machine trouble code…
Vehicles: Eco Esporte, Fiesta and Ka. More ECU PINOUT Components: ECU Modules Repair Pinpout…
Wabco software is designed to facilitate the configuration of the Trailer EBS – ABS Braking…
This instruction show you guide on how to remove and install water pump for HINO…
JPRO 2025V3 CTIS Pressure test allow you to measure the pressure of a selected axle group…