How to Solve PCC1302 Code 1472 High AC Current Shutdown

This instruction show you guide on how to solve PCC1302 PowerCommand Code 1472 high AC current shutdown.

Related Contents:

2024 InPower V14.5 Pro V12 Diagnostic Software Free Download

PowerCommand Diagnostic 9 Pin Adapter Cable for InPower

 

 

Logic:
The generator output current has exceeded at least 150% of rated current.

Possible Causes:
1 Short or overload

2 Incorrect CTs, CT connections, or CT setup
3 CT harness connections
4 Incorrect rating setup

Diagnosis and Repair:
1 Short or overload

a Inspect the load cables and the AC harness connections.
b Disconnect the AC harness from the load cables.
c Inspect the AC harness and board connector pins.
d Visually inspect for corroded pins, bent or broken pins, pushed back or expanded pins.
e Check for a short circuit to engine block ground.

2 Incorrect CTs, CT connections, or CT setup
a Check CTs.
a Check that correct CT’s have been installed.
b Check that CT connections are secure by zip ties to corresponding wires.
c Check that CTs are installed in the correct order.
d Connect InPower.
e Verify the correct CT ratio has been entered in the generator setup.
f Adjust the setting(s) as necessary.

3 CT harness connections
a Measure the resistance of the CT harness on each pin.
b Disconnect connector P12 from the control board and CTs.
c Verify the resistance from board connector to CT connections. Resistance should be 5 ohms or less.
d Measure the resistance of each pin on the CT harness connector to engine block ground. Resistance should be open or infinite.
e Verify the CT connections are correct from P12 to the CT terminals.
P12–1 (CT1) to P12–4 (CT1–COM)
P12–2 (CT2) to P12–5 (CT2–COM)
P12–3 (CT3) to P12–6 (CT3–COM)
f Re-terminate connections as necessary.

4 Incorrect rating setup
a Connect InPower.
b Verify the generator rating in the control is set correctly.
c Verify CT ratings in the control are set correctly.
d Adjust settings as necessary

auto

Recent Posts

Caterpillar C9 Engine Throttle Position Out of Calibration 28 91-13 Trouble Solution

This instruction show you guide on how how to solve trouble code 28 PID 91-13…

2 days ago

Magneti Marelli 1 AVB-VW ECU Pinout

Vehicles: With AP 1.6, 1.8 and 2.0 Ml engines DE 97 to 99. And for…

4 days ago

Valtra BH Series 140-210 Internal lateral Inertial Sensor Recalibration

This instruction show you guide on how to solve Valtra BH Series 140-210 trouble code SA…

5 days ago

Bendix AutoVue 3G LDW System Driver Assistance Systems (DAS) Tests

JPRO 2025V3 Driver Assistance Systems (DAS) Tests allows the editing of configuration parameters.   Related Contents:…

1 week ago

How to Solve PCC2300 PowerCommand Membrane Buttons Not Functioning

This instruction show you guide on how to solve PCC2300 Powercommand Membrane buttons not working.…

2 weeks ago

How to Solve JCB JS140 Excavator C101E Fuel Level Empty Alarm Error?

This instruction show you guide on how to solve JCB JS140 excavator C101E-68 fuel level…

2 weeks ago